| TYPE | True three-phase transformer turns-ratio tester | 
                  
                    | PHYSICAL SPECIFICATIONS | 21”W x 9”H x 17”D (53 cm x 24 cm x 43 cm); Weight: 35 lbs (15.8 Kg) | 
                  
                    | INPUT POWER | 3 amps, 100 – 240 Vac, 50/60 Hz | 
                  
                    | MEASUREMENT METHOD |  | 
                  
                    | TURNS-RATIO MEASURING RANGE | 0.8 – 15,000 (5-digit resolution) | 
                  
                    | TURNS-RATIO ACCURACY | 0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 8 Vac 0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 40 Vac
 0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 100 Vac
 | 
                  
                    | TEST VOLTAGES | Three-phase, 8 Vac @ 1 Amp, 40 Vac @ 0.2 Amps, 100 Vac @ 0.1 Amp | 
                  
                    | EXCITATION CURRENT READING RANGE | 0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA) | 
                  
                    | PHASE ANGLE MEASUREMENT | 0 – 360 degrees; Accuracy: ± 0.2 degree (± 1 digit) | 
                  
                    | DISPLAY | Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels | 
                  
                    | PRINTER | Built-in 4.5-inch wide thermal printer | 
                  
                    | EXTERNAL DATA STORAGE | One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included). | 
                  
                    | COMPUTER INTERFACES | One RS-232C port, One USB port | 
                  
                    | PC SOFTWARE | Windows XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price | 
                  
                    | INTERNAL TEST RECORD STORAGE | Stores up to 112 transformer test records. Each record holds the test record header and up to 33 readings. | 
                  
                    | INTERNAL TEST PLAN STORAGE | Stores up to 128 transformer test plans. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface | 
                  
                    | LOAD TAP CHANGER CONTACT | 240 Vac, 1 Amp | 
                  
                    | SAFETY |  | 
                  
                    | ENVIRONMENT | Operating: -10° to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F) | 
                  
                    | CABLES | One 15-foot single-phase set, One 15-foot three-phase set, One 25- foot extension set, One ground cable, One USB cable, One RS-232C cable, power cord, cable bag | 
                  
                    | OPTIONS | Transportation case | 
                  
                    | WARRANTY | One year on parts and labor | 
                  
                    | Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). Last updated on February 16, 2009
 |