| MCE ADV STANDARD CONTROLLERDescription
 Power factor  controllers MCE-6 ADV (6 steps) and MCE-12 ADV (12 steps) measure the cos φ of  a supply system and control the automatic connection and disconnection of compensation  capacitors, according to desired cos φ.
 Technical Characteristics
 Supply and measurement voltage (C-D)  ........... 230/400/480 V
 
  Frequency  range ................................... 45 ... 65 Hz (automatic adjust)  Power consumption MCE ADV-6 .............3VA (no relays)  y/and 5,5VA (6 relays on)MCE ADV-12............4VA (no relays) y/and 8,5VA (12 relays on)
 External current transformer  ................... …/5 A (not included)
 Accuracy of voltage measurement  ...................... 1%
 Working program selection  ...................... 1.1.1.1., 1.2.2.2., 1.2.4.4., 1.2.4.8. y/and 1.1.2.2.
 Adjustment of cos φ..........................................  0.85 Ind – 0.95 Cap (digital)
 LCD Display  ........................................ 1 line x 3 digits x 7 segments + 20 icons
 Lectura del cos φ/Lecture of cos φ  ......................... Display LCD
 Accuracy of cos φ measurement  ........................... 2% ± 1 digit
 Adjustment of C/K factor  ................................................ 0.02 ... 1 (digital)
 Connection time between steps .......... 4 ... 999 sec. (10s default)
 Reconnection time of capacitors  .............................. 5 times T connection
 Climatic range ..............  -10/+50oC
 Wiring  ....................................................... Connection terminal
 Degree of protection ........   mounted on panel board ( )
 Safety/Insulation ...........  , Cat. III Ambiente 2/Environment 2.
 Dimensions ........................  144x144mm (hole 138x138mm)
 Total depth  ................................ 60mm
 Weight  ........................................ 538g
 Selection the number of output  relays.......................MCE ADV-12: 12 relays
 Control strategy ..................  FCP (algorism to minimize switching operations )
 Output relays contacts.................................  4 A/ 250V AC1
 Standards  ....................................................
 
  
    | Part number | Model | Power (V) | Size (mm) | Steps | Price() |  
    | MCE06ADV230 | MCE ADV 6 | 230 | 144x144 | 6 | 241,50 |  
    | MCE06ADV400 | MCE ADV 6 | 400 | 144x144 | 6 | 220,50 |  
    | MCE12ADV230 | MCE ADV 12 | 230 | 144x144 | 12 | 330,75 |  
    | MCE12ADV400 | MCE ADV 12 | 400 | 144x144 | 12 | 315,00 |  Plug and PlayA series of  parameters must be configured when a power factor regulator is installed, to  make sure that it operates correctly. Some of these parameters might be hard to  know, such as, for example, the voltage phases or the voltage corresponding to  the current measured, as well as the current transformer ratio. MCE ADV has  been designed with a smart automatic process that detects the necessary  parameters, such as:
 C/K: calculates the ratio of the current  transformer and the power of the smallest step.
 Phase: Identifies the voltage sequence  and correspondence with current. In other words, it identifies the UL1, UL2, UL3,  when the current measured is IL1, IL2, IL3 and whether it is connected in the  opposite way or not.
 Number of stages  installed and Program:  the system connects  all stages in a sequence,  finds out how many  stages are installed  and then calculates  the program, i.e., the power ratio  of the capacitors.
 FEATURES
 1. i Mproved setting  up configuration when  commissioning Phase
 Installation and  polarity of the CT (Current Transformer). This controller avoids user to switch  phases and polarity (cabling) of CT (X/5) connection. Now, user can adjust it  and set it up through display menu on the MCE ADV; indicating what phase it is  installed and the polarity of the CT.
 2. v alues /  Measures in the  network
 - Current (A)
 Total RMS current (A) measured from the CT  (X/5).
 - Voltage (V)
 Phase RMS voltage (V) measured from the  capacitor bank main copper bars.
 - THD (%) in  Current (A)
 Current (A) Harmonic distortion (%) in the  network.
 - MAX (A) &  (V) Recording
 MCE ADV is  recording the maximum phase current and voltage values measured from the CT  (X/5) connection and from the capacitor bank main copper bars, respectively.
 3. Event alarms by  led and relay
 MCE ADV comes with  alarm events warnings, whether by LED or RELAY, in case of these  circumstances:
 - Lack of  compensation
 -  Over-compensation
 - Over-voltage
 - Over-current
 - CT unplugged
 - Current below  the limits
 
 (Note: to perform  alarm relay, there must be available at least one step relay)
 Reactive power controllers
 MCE ADV|     | 
 MCE06ADV230 MCE ADV 6
MCE06ADV400 MCE ADV 6
MCE12ADV230 MCE ADV 12
MCE12ADV400 MCE ADV 12
 Reactive Power ControllersDescription
 Reactive power  controllers MCE ADV, PFCL and MASTER are designed to measure the reactive power  of an installation and to give the necessary instructions for connecting and  disconnecting capacitors in order to maintain the desired cos φ .
 All the  controllers are commanded by a microprocessor that ensures an uniform ageing of  contactors and capacitors by using a circular connection sequence that takes  into account the time that each capacitor has been switched on.
 Power factor value  to be reached can be adjusted in a continuous way, between 0.85 inductive and  0.95 capacitive.
 Standard working programs  for controllers are 1:1:1:1,
 1:2:2:2, 1:2:4:4,  1:2:4:8 and 1:1:2:2.
 Advantages
 Uniform ageing of the capacitors and  contactors
 High speed operation with less number of  switchings
 True rms measuring circuit, insensitive to  harmonics
 Automatic disconnection of all the  capacitors in the case of
 a failure in the electrical network
 Detection and automatic indication of  current transformer
 wrongly connected
 Digital cos φ display
 Adjustable operation delay
 Power factor alarm relay (PFCL/MASTER)
 Harmonic distortion alarm relay  (PFCL/MASTER)
 Some others advanced features, depending  on the model.
 Range
 MCE ADV, of  6 or 12 steps, for standard automatic  bank.
 PFCL,  available with 6 and 12 relays, size 144x144mm with special alarms and  communication.
 MASTER,  available with 6, 12 and 14 relays, size 144x144mm with special alarms and communication.
 |    | 
 |