| TYPE | Portable relay test set | 
            
              | INPUT POWER | 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz | 
            
              | PHYSICAL SPECIFICATIONS | 17”W x 12.5”H x 12”D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg) | 
            
              | AMPERE METER INPUT RANGES | Internal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA, External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA
 External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
 Measurement Method: True RMS for AC
 | 
            
              | VOLT METER INPUT RANGE | 0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count Measurement Method: True RMS for AC
 | 
            
              | AUXILIARY POWER SUPPLIES | 24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A | 
            
              | POWER RESISTORS | 5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W | 
            
              | SAFETY |  | 
            
              | ENVIRONMENT | Operating: -10C to 50 C (15F to +122 F); Storage: -30 C to 70 C (-22F to +158 F) | 
            
              | OPTIONS | Transportation case | 
            
              | WARRANTY | One year on parts and labor | 
            
              | AC Current Output | 
            
              | 
                
                  
                    | Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times |  
                    | 10 A | 90 Vac | 75 Vac | 10 A | 2 min / 15 min |  
                    | 40 A | 25 Vac | 20 Vac | 40 A | 1 min / 15 min |  
                    | 100 A | 10 Vac | 7.25 Vac | 100 A | 1 min / 15 min |  
                    | 100 A | 10 Vac | 3 Vac | 250 A | 1 sec / 5 min |  | 
            
              | AC Voltage Output | 
            
              | 
                
                  
                    | Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times |  
                    | 250 Vac | 260 Vac | 240 Vac | 3 A | 10 min / 45 min |  | 
            
              | DC Voltage Output | 
            
              | 
                
                  
                    | Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times |  
                    | 300 Vdc | 300 Vdc | 250 Vdc | 2 A | 10 min / 45 min |  | 
            
              | RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable) | 
            
              | 
                
                  
                    | Range | Resolution | Accuracy |  
                    | 0 to 9.999 sec | 1 ms | ± (1 ms + 0.01%) |  
                    | 10.00 to 99.99 sec | 10 ms | ± (10 ms + 0.01%) |  
                    | 100.0 to 999.999 sec | 100 ms | ± (100 ms + 0.01%) |  | 
            
              | Timer Cycles Display | 
            
              | 
                
                  
                    | Range | Resolution | Accuracy |  
                    | 0 to 9.999 cycles | 0.1 cycle | ± (0.1 cycle + 0.01%) |  
                    | 1,000 to 49,999 cycles / 50 Hz | 1 cycle | ± (1 cycle + 0.01%) |  | 
            
              | Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). |