| TYPE | Portable, lightweight, automatic, 3-phase transformer turns-ratio meter | 
                  
                    | PHYSICAL SPECIFICATIONS | 20”W x 7.5”H x 15.5”D (50 cm x 19 cm x 39.6 cm); Weight: 27 lbs (12 kg) | 
                  
                    | OPERATING VOLTAGE | 100 – 240 Vac, 50/60 Hz | 
                  
                    | BATTERIES | Two lead acid batteries (12V, 2 AH) provide up to 3 hours of operation | 
                  
                    | MEASUREMENT METHOD |  | 
                  
                    | TURNS-RATIO MEASURING RANGE | 0.8 – 15,000 | 
                  
                    | TURNS-RATIO ACCURACY | 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 15,000: ±1% @ 8 Vac 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 15,000: ±1% @ 40 Vac
 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 15,000: ±1% @ 100 Vac
 | 
                  
                    | TEST VOLTAGES | 8 Vac @ 350 mA, 40 Vac @70 mA, 100 Vac @ 20 mA | 
                  
                    | EXCITATION CURRENT READING RANGE | 0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA) | 
                  
                    | PHASE-ANGLE MEASUREMENT | 0 – 360 degrees; Accuracy: ±0.2 degree ( ±1 digit) | 
                  
                    | DISPLAY | Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels | 
                  
                    | PRINTER | Built-in 4.5-inch wide thermal printer | 
                  
                    | COMPUTER INTERFACES | One RS-232C port, One USB port | 
                  
                    | EXTERNAL DATA STORAGE | One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included). | 
                  
                    | PC SOFTWARE | Windows XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price | 
                  
                    | INTERNAL TEST RECORD STORAGE | The unit can store 112 transformer test records. Each record holds the test record header and up to 33 readings. | 
                  
                    | INTERNAL TEST PLAN STORAGE | The unit can store 128 transformer test plans. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface | 
                  
                    | LOAD TAP CHANGER CONTACT | 240 Vac, 1 Amp | 
                  
                    | SAFETY |  | 
                  
                    | ENVIRONMENT | Operating: -10 to 50 C (15 to +122 F); Storage: -30 C to 70 C (-22 to +158 F) | 
                  
                    | CABLES | One 15-foot single-phase set, One 15-foot 3-phase set, one 25-foot extension set, One safety ground, One USB, One RS-232, One LTC cable, cable bag | 
                  
                    | OPTIONS | Transportation case | 
                  
                    | WARRANTY | One year on parts and labor | 
                  
                    | Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). Last updated on February 16, 2009
 |