| TYPE | Portable circuit-breaker analyzer | 
| PHYSICAL SPECIFICATIONS | 14”W x 21 K” L x 8” D (35 cm x 53 cm x 20 cm); 15 lbs (6.8 Kg) | 
| INPUT POWER | 100-240Vac, 3A, 50/60Hz | 
| DRY-CONTACT INPUTS | 3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time. | 
| TIMING WINDOWS | 1 second, 10 seconds, or 20 seconds | 
| TIMING RESOLUTIONS | ±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration,
 ±1.0 milli-seconds @ 20 sec. duration
 | 
| TIMING ACCURACY | 0.05% of reading ±0.05 ms @ 1 second duration | 
| DRY-CONTACT CHANNEL PROTECTION | All contact inputs are grounded until test. Input channels are also protected against static discharge. | 
| DRY-CONTACT DETECTION RANGE | Closed: Less than 20 Ohm. Opened: greater than 5000 ohm | 
| INSERTION RESISTOR DETECTION RANGE | 50 – 5,000 ohms | 
| TRIGGER INPUT VOLTAGE | Open/Close trigger voltage: 24 V – 300V DC or peak AC | 
| VOLTAGE SENSING INPUT RANGE | V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
 | 
| BREAKER OPERATIONS | Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open | 
| BREAKER INITIATE CAPACITY | 30A, 250 Vac/dc max | 
| INITIATE CURRENT READING RANGE | one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC | 
| DIGITAL TRAVEL TRANSDUCER INPUTS | 3 channels, 200 ohm – 10K ohms | 
| CONTACT TRAVEL POINT DIFFERENCE | measures “slow-close” contact-point distances; results can be printed | 
| DISPLAY | back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light | 
| PRINTER | built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results | 
| INTERNAL TEST RECORD STORAGE | Store up to 200 test records and 100 test plans | 
| EXTERNAL TEST RECORD STORAGE | USB Flash drive interface for external storage of test records and test plans | 
| COMPUTER INTERFACES | One USB port, optional Bluetooth wireless interface | 
| PC SOFTWARE | Windows? based Breaker Analysis software included with purchase price | 
| CABLES | furnished with full set of test leads | 
| OPTIONS | transportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode, bluetooth interface
 | 
| SAFETY |  | 
| ENVIRONMENT | Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F) | 
| HUMIDITY | 90% RH @ 40°C (104°F) non-condensing | 
| ALTITUDE | 2,000 m (6,562 ft) to full safety specifi cations | 
| WARRANTY | one year on parts and labor | 
| Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F). |