| TYPE | Portable digital circuit breaker analyzer | 
            
              | PHYSICAL SPECIFICATIONS | 18.5”W x 14”H x 7”D (47.0 cm x 35.7 cm x 17.6 cm); Weight: 16 lbs (7.3 kg)
 | 
            
              | INPUT POWER | 3 Amps, 100 – 240 Vac, 50/60 Hz | 
            
              | DRY-CONTACT INPUTS | 3 dry-contact channels; each channel detects main contact and insertion resistor contact | 
            
              | TIMING WINDOWS | 1-second, 10-seconds, or 20-seconds | 
            
              | TIMING RESOLUTIONS | ±50 micro-seconds @ 1-second duration, ±500 micro-seconds @ 10-second duration, ±1.00 milli-second @ 20-second duration | 
            
              | TIMING ACCURACY | 0.05% of reading ±0.1 ms @ 1-second duration | 
            
              | CONTACT DETECTION RANGE | Closed: less than 20 ohms; Open: greater than 5,000 ohm | 
            
              | RESISTOR DETECTION RANGE | 50 – 5,000 ohms | 
            
              | TRIGGER INPUT VOLTAGE | Open/Close: 30 – 300V, DC or peak AC | 
            
              | VOLTAGE SENSING INPUT RANGE | V1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC
 | 
            
              | BREAKER OPERATIONS | Initiate Open, Close, Open – Close, Close – Open, Open – Close – Open | 
            
              | BREAKER INITIATE CAPACITY | 30A, 250 Vac/dc max | 
            
              | INITIATE CURRENT READING RANGE | One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz | 
            
              | TRAVEL TRANSDUCER INPUT | 1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.); Rotary range: 0 – 360 degrees (±0.006 degrees) | 
            
              | CONTACT TRAVEL POINT DIFFERENCE | Measures “slow-close” contact-point distances; results can be printed | 
            
              | CT CURRENT SENSOR | One, non-contact, 0 – 100A | 
            
              | COMPUTER INTERFACES | One USB port, optional Bluetooth interface | 
            
              | PC SOFTWARE | Windows-based Vanguard Circuit Breaker Analysis (VCBA S2) software is included with purchase price. Software updates available at no additional charge. | 
            
              | SAFETY |  | 
            
              | ENVIRONMENT | Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F) | 
            
              | OPTIONS | Transportation case (available for the DigiTMR S2 and the travel transducers) | 
            
              | WARRANTY | One year on parts and labor | 
            
              | Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). |