| TYPE | Portable current-transformer test set | 
                  
                    | PHYSICAL SPECIFICATIONS | 19”W X 13”H x 15.8” D (48.3 cm x 33.0 cm x 40.1 cm); Weight: 73 lbs (33.1 kg) | 
                  
                    | INPUT POWER | 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz | 
                  
                    | MEASUREMENT METHOD |  | 
                  
                    | TEST OUTPUT VOLTAGES | 0 – 50 Vac @ 10A max; 0 – 300 Vac @ 10A max; 0 – 500 Vac @ 5A max; 0 – 1200 Vac @ 1.2A max; 0 – 2000 Vac @ 1A max | 
                  
                    | CURRENT SOURCE | 1 – 20A @ 0 – 15 Vac | 
                  
                    | CURRENT SOURCE DISPLAY | Test current and current on-time | 
                  
                    | VOLTAGEREADING RANGE | 0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 V | 
                  
                    | CURRENTREADING RANGE | 0 – 10A; Accuracy: ±1.0% of reading, ±0.02A | 
                  
                    | CT CURRENT RATIO RANGE | 0.8 – 999: 0.1%; 1000 – 1999: 0.3%; 2,000 – 5,000: 1% | 
                  
                    | PHASE ANGLE MEASUREMENT | 0 – 360 degrees; Accuracy: ± 1.0 degree) | 
                  
                    | RESISTANCEREADING RANGE | 100 micro-ohms – 10 ohms; Accuracy: 2% of reading, ± 1 count | 
                  
                    | INSULATIONRESISTANCE READING RANGE | 2 Mega-ohms – 500 Mega-ohms; Accuracy: 3% of reading, 500 – 1000 Vdc test voltage | 
                  
                    | DISPLAY | Back-lit LCD Screen 240 x 128 dot graphic; 114mm x 64mm
 Viewable in bright sunlight and low-light levels
 | 
                  
                    | PRINTER | Built-in 4.5-inch wide thermal printer | 
                  
                    | COMPUTER INTERFACES | One RS-232C (115,000 Baud) port, One USB port | 
                  
                    | EXTERNAL DATA STORAGE | One USB Flash drive interface port | 
                  
                    | PC SOFTWARE | Windows XP/Vista-based CT Analysis software is included with the purchase price | 
                  
                    | INTERNAL TEST RECORD STORAGE | Stores 140 test records. Each test record may contain up to 10 saturation curves, current-ratio readings, and polarity and DC resistance readings | 
                  
                    | INTERNAL TEST PLAN STORAGE | Stores 128 test plans. A test plan consists of the saturation test voltage, current selection, CT nameplate ratios, and CT winding terminal combinations (X1 to X5) for each test | 
                  
                    | SAFETY |  | 
                  
                    | ENVIRONMENT | Operating: -10°C to 50°C (15°F to +122°F); Storage: -30°C to 70°C (-22°F to +158°F) | 
                  
                    | CABLES | Five 20-foot X cable sets, One 35-foot H cable set, current source cables, insulation test cables, power cord, ground cable. A transportation case is included with the purchase price. | 
                  
                    | WARRANTY | One year on parts and labor | 
                  
                    | Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). Last updated on March 16, 2009
 |