                                                  | 2820 EL   ELCB Testers Up To 1000mA
 |  
                                                  |  |  | 
                                                
                                                
                                                  | FEATURES |  
                                                  |  |  
                                                  |  Operating voltage 100-450V L-E. |  
                                                  |  Rated current 999mA, at 317V AC/50Hz. |  
                                                  |  Checks ELCB trip time and trip point (sensitivity). |  
                                                  |  Auto-Off/Auto-Ranging. |  
                                                  |  Phase angle selection (0 degree / 180 degree). |  
                                                  |  Indicates tripping phase angle. |  
                                                  |  Impact resistant enclosure. |  
                                                  |  Over temperature shut-down. |  
                                                  |  Transient protection. |  
                                                  |  Suitable for heavy industrial use. |  
                                                  |  Fused. |  
                                                  |  , -1 CAT III 450V. |  | 
                                          
                                            | 
                                                
                                                
                                                  |  OPERATING PRINCIPLES |  
                                                  |  EARTH LEAKAGE TESTS |  
                                                  |  The testers may be used to check the trip point (Test 1) of the ECLB or the trip time (Test 2). Test 1 is normally used on instantaneous ELCBs while Test 2 is normally used on inverse and fixed time-delay ELCBs. |  
                                                  |  TEST PROCEDURE |  
                                                  |  Test 1 - instantaneous ELCBs A ramp current, increasing at approximately 12 mA/s is introduced between L and E and the point at which the ELCB trips is recorded. To save time and reduce energy dissipation, the starting point of the ramp may be selected. |  
                                                  |  Test 2 - inverse and fixed time delay ELCBs. Aconstant current is selected and injected between L-E and the tripping time is recorded. |  | 
                                          
                                            | 
                                                
                                                
                                                  | SPECIFICATIONS |  
                                                  |  |  
                                                  | Trip Current-Range | 0-1 A at 317V (Auto-Range Programmable) |  
                                                  | Trip Current-Resolution | 1mA |  
                                                  | Operating Voltage (L-E) | 100-450V |  
                                                  | Phase Angle Setting | 0 degree and 180 degree selectable |  
                                                  | Timer-Max | 99.999s |  
                                                  | Timer-Resolution | 1mS |  
                                                  | Typical Accuracy |  |  
                                                  | Trip-Current | +/- 1%rdg +/-1mA |  
                                                  | Trip-Time | +/- 1%rdg +/-1dgt |  
                                                  | Voltage | +/- 3%rdg +/-1dgt |  
                                                  | Operating-Temperature-Humidity | -10 degree C to + 40 degree C, 80% max relative humidity |  
                                                  | Power Source | 1.5V (AA) x 8 batteries |  
                                                  | Dimensions | 170(L) x 120(W) x 95(D) mm |  
                                                  | Weight | Approx. 800g (battery included) |  
                                                  | Accessories | Test leads |  
                                                  |  | Shoulder belt |  
                                                  |  | Instruction manual |  
                                                  |  | Batteries |  |